Harmonics In Electrical Networks
The harmonic is defined as one of the components obtained from the breakdown of a periodic wave in the Fourier series. The order of a harmonic is further defined as the ratio between the frequency of the harmonic and the fundamental frequency of the periodic wave considered.
In the case of the perfectly sinusoidal waveform (as should characterize the voltage supplied by the utility) only the fundamental harmonic of the first order will be present, which in India has a frequency of 50 Hz.
If a sinusoidal voltage is applied to a load, the circulating current will also have a sinusoidal waveform only in the presence of loads with “linear characteristics”.
In the presence of a “non-linear” load the current waveform will deviate from the ideal pattern and breaking down the wave according to the Fourier theorem will show evidence of harmonics whose number and amplitude will increase with the degree of distortion in the current waveform.
The increasingly frequent use of non-linear loads in industrial facilities (inverters, fluorescent lamps, welders, DC drives etc.) Creates elevated distortions in the waveform of circulating current.
This is true in the case of ac/dc converters, for which the input current theoretically displays only harmonics of the order.
h=mp±1
The parameter used to determine the level of harmonic distortion presents in an electrical network is
THD% of voltage & current.
Negative Effects of Harmonics
-
The capacitors are subjected to a
voltageoverload and their lifetime is
drastically reduced.
-
Connection of the capacitor causes a
large increase in the distortion factors
THD(V) & THD (I).
-
Motors; Reduced motor life, inability to
fully load motor.
-
The user transformers, wires and loads
are affected by this increase in
current, which leads to increased I R
losses and eddy current losses in
transformer. This reduces the capacity
of transformer resulting into economic
loss as well.Apart from this transformer
may also be subjected to excessive
overheating and saturation.
-
Interference in computers,
microprocessor & solid state controlled
equipment because of distorted 240 V
supply. Increased neutral to ground
voltage may cause hardware problems
which may initially look like software
problem.
-
High voltage distortion shall also be
encountered when shifting from mains to
emergency generator as they offer high
impedance than supply transformer.
-
Large current in neutral wires of power
distribution system. This is a real fire
hazard as usually phase wires are
protected by circuit breakers or fuses.
-
Poor power factor: As mentioned earlier
the harmonic current caused by
non-linear loads do not carry any real
power (KW) even though they do increase
the volt amperage (KVA). This lowers the
power factor at (Pf=KW/KVA) the main
distribution transformer. Utilities put
penalties on consumers with low P. F.,
less than 0.9.
-
Over heating in fuses resulting in false
blowing. False / spurious operations of
breakers, which may lead to variation in
other characteristics.
What do P. F. Correction Capacitors have to do with Harmonics ?
In an industrial plant containing power
factor correction capacitors, harmonics
distortions can be magnified due to the
interaction between the capacitors and the
service transformer. This is referred to as
harmonic resonance or parallel resonance. It is
important to note that capacitors themselves are
not main cause of harmonics, but only aggravate
potential harmonic problems. Often,
harmonic-related problems do not show up until
capacitors are applied for power factor
correction.
Components of Detuned Systems Controller - Single Phase or 3 Phase
-
Measurement of A, V, PF, CosΦ,
W, Var, VA (∑W,
∑VA, ∑VAr etc.)
-
Sense1%of load current
-
Auto/Manual mode selection with indicator light
-
Automatic calculation of C/k value
-
Program entry for targeted CosΦ
value
-
Number of capacitor steps are user definable
-
The consequent switching time between capacitor
steps is adjustable from 2 to 50 sec.
-
C+/NORMAL/C- condition lights indicate actual
system state.
-
Over Voltage Insufficient Compensation, Over
Compensation state alarm indicator lights with
output contact
-
Adjustable programmable Over Voltage protection
for capacitor banks.
-
Micro Controller based digital design complying
with international standards.
-
Flush mounting with rear panel connectors.
-
Designed to use with Current T/F (.../5A)
Data Logger Module with Energy Analyzer (Optional)
Energy Analyzer with Data Logger is having
facility to record and display all the 3 Phase
parameters of
mains where P.F.C. system is connected.
Capacitors Banks
Neptune-Ducati ranges of Capacitor Banks are using Capacitor Modules from M/s Ducati energia s.p.a,Italy. Ducati energia is a leading company in production of power factor correction capacitors. Following this tradition, continuous investments in research and development of new products have represented the policy of the company.
The result of this philosophy is the new range of Long Life Capacitors MONO16 and MODULO50. Thanks to the technological innovation of self-healing metallized polypropylene; the rated power of 50 KVAR is achieved in just one 3- phase element with very compact dimensions & a much higher life expectancy in comparison with other models. These new Long-Life Capacitors Mono16 & Modulo50 reach an expected life of more than 160,000 hours and a size reduction up
to 40% against the technologies so far applied with low loss of 0.2W/KVAR with 4 In capabilities and oil impregnation, the performance of these capacitors are much better in comparison to other technologies
available in market like gas filled & dry type.
Harmonic Reactors
Neptune Filter Circuits are designed as three-phase reactors with an iron core and air gap. Harmonic Filter Reactors are made out of high quality material and very stringent quality control. It has been designed with properties like low temperature rise and lower flux density so that it can operate in worst conditions of ambient and harmonic overloads.
They offer very good degree of linearity and low losses.Cheaper and non- linear reactors may trigger undesirable chain phenomena during periods of operation with high harmonic values, such as reduction in the inductance with consequent increase in the resonance frequency of the LC group, which would drain off more harmonic current, further reducing its inductance and overload the reactor more and more. Reactors are available with filtering factor of 5.6%, 7% and 14% as per standard ratings. Any other filtering factor and rating can be developed on request.
Other parts of Detuned systems.
- Other parts of Detuned systems.
- HRC Fuses
- ACB and MCCB as Incomer
Activcomp
Neptune can also offer fast Thyristor
switched transient free system for power
factor correction & harmonic filtration.
Electrical & General Characteristics:
- Power range: 125 - 1000 KVAR
(440V)
- Mains working voltage- 415-440V (other
voltages on request)
- Rated frequency :50 Hz
- Altitude: 2000ma.s.l.
- Relative humidity: 70% max. at 20 C
- Duty :continuous
- Ambient temperature class:-5+ 45 C
- Power supply line:
Three-phase + ground +
neutral (for control only) in 3 phase
controller
- 3 phase + ground in single phase
controller.
- Relay current input signal: from 3 no’s
or 1no.CT on line.../5A as per controller type.
- Relay voltage input signal: picked up
internally.
|